industrial battery charging points in three ways: a floating charge (float); equalizing charge (charging); recycling charge details, see the site "battery charging" series of knowledge. This article describes the precautions in the battery charging. Charging precautions in If charging the end of the charging current of more than 0.05C10A may cause permanent damage to the battery appearance and life, please pay special attention to the charging voltage. Recycling, in order to prevent overcharge, it is recommended to install a timer or take automatically be converted to trickle charge after fully charged. When the ambient temperature is 25 ℃, the response to set the voltage temperature compensation, the formula: Correction U = U25 ℃-K × (T actual -25) (T actual - ambient temperature, the K-temperature compensation coefficients) Battery charge termination is the basis to judge Under normal circumstances, when the battery charge to achieve one of the following conditions can be regarded as charge termination. 1), charge into the power to release the power of 1.1 ~ 1.3 times. 2), charging late charge current is less than 0.005C10A (C10 = rated capacity of the battery). 3) charging late charge current for 5 hours does not change.
...